Справочник Пользователя для Mitsubishi Electronics MELSEC Q series MELSEC L series

Скачать
Страница из 412
5-210
5.4 Network Dedicated Instruction
5.4.22 REMFR instruction
Z_REMFR
5.4.22  
REMFR instruction
Z_REMFR
*1: Local devices and file registers per program cannot be used as setting data.
Z(P)_REMFR
P: Executing condition
:
 indicates any of the following 
instructions.
Z_REMFR
ZP_REMFR 
Input argument
EN:
Executing condition
:Bit
Jn*:
Target network number (1 to 239)
:String
n1:
Channel number (1 to 32)
:ANY16
n2:
Target station number (1 to 120)
:ANY16
n3:
Start I/O number of the target intelligent function module
For the CC-Link IE Field Network, the higher two digits when 
expressing the I/O number in three digits.
For the MELSECNET/H, the higher three digits when 
expressing the I/O number in four digits.
:ANY16
n4:
Read buffer memory start address
Specifies the start address of the buffer memory for the read 
destination intelligent function module.
:ANY16
n5:
Number of read points (1 to 240 words)
:ANY16
Output argument
ENO:
Execution result
:Bit
d1:
Start number of the device that stores read data (host station)
Specifies the start number of the host station's device that 
stores read data.
:ANY16
d2:
Variable that turns ON upon completion of the instruction
d2[1] also turns ON at the time of error completion.
:Array of bit [0..1]
Setting
data 
*1
Internal device
R, ZR
J
\
U
\G
Zn
Constant
K, H
Others
Bit
Word
Bit
Word
n1
n2
n3
n4
n5
CC IE F NET/H
Structured ladder/FBD
EN
ENO
Jn*
d1
d2
n1
n2
n3
n4
n5
Z_REMFR
ST
Z_REMFR
(EN, Jn*, n1, n2, n3, n4, n5, d1, d2);
ENO:=
d1
d2