Справочник Пользователя для Mitsubishi Electronics MELSEC Q series MELSEC L series

Скачать
Страница из 412
5-28
5.1 Analog Instruction
5.1.3 OGSTOR instruction
G_OGSTOR
5.1.3  
OGSTOR instruction
G_OGSTOR
*1: Local devices and file registers per program cannot be used as setting data.
Function
This instruction restores the user range settings offset/gain values stored in the programmable 
controller CPU to the analog modules.
G(P)_OGSTOR
P: Executing condition
:
 indicates any of the following 
instructions.
G_OGSTOR
GP_OGSTOR
Input argument
EN:
Executing condition
:Bit
Un*:
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/O number in 
three digits)
:ANY16
s:
Variable that stores control data
:Array of ANY16 [0..35]
Output argument
ENO:
Execution result
:Bit
d:
Variable that turns ON upon completion of the instruction
d[1] also turns ON at the time of error completion.
:Array of bit [0..1]
Setting
data 
*1
Internal device
R, ZR
J
\
U
\G
Zn
Constant Others
Bit
Word
Bit
Word
Structured ladder/FBD
ST
G_OGSTOR
EN
ENO
d
Un*
s
G_OGSTOR
(EN, Un*, s, d);
ENO:=
s
d