5   DATA LINK PROCESSING TIME 
MELSEC-QnA 
 
5.4.3 Master station   intelligent device station 
(1)   Master station   intelligent device station 
Indicates the time from when the master station issues an instruction until it 
receives a reply from an intelligent device station. 
 
[Expression] 
(a)   For reading 
MB = [SM + LS × 2 + 
α + SM + LS × 2 + {(No. of reading points + 16)/16}
 × LS + 
β + constant bps] × N [ms] 
SM : Master station sequence scan time 
LS  : Link scan time (Refer to section 5.2) 
α  : Send end internal processing time 
 
No. of reading points 
1 to 120 points 
121 to 240 points 
241 to 360 points 
361 to 480 points 
α 
LS 
LS × 2 
LS × 3 
LS × 4 
β  : Receive end internal processing time 
LS 
[Constant bps] 
 
Transmission speed 
156kbps 
625kbps 
2.5Mbps 
5Mbps 
10Mbps 
constant bps 
LS 
LS × 2 
LS × 4 
LS × 6 
LS × 7 
N  : No. of execution instructions simultaneously 
1 : Raise the decimals to a unit 
 
(Example) When master station sequence scan time is 10ms, link scan time is 5ms, 
no. of reading points is 20 words, transmission speed is 10Mbps, no. of 
execution instructions simultaneously is 1 
MB = [SM + LS × 2 + 
α + SM + LS × 2 + {(No. of reading points + 16)/16}
 × LS + 
β + constant bps] × N 
= [10 + 5 × 2 + 5 + 10 + 5 × 2 + {(20 + 16)/16}
1
 × 5 + 5 + 5 × 7] × 1 
= [10 + 5 × 2 + 5 + 10 + 5 × 2 + 3 × 5 + 5 + 5 × 7] × 1 
= 100 [ms]