6 - 4 
6   PARAMETER SETTING 
MELSEC-QnA 
 
6.2 Parameter Settings 
The items to set in the master station's "parameter information area (address 0
H
 to 
5F
H
)" in the buffer memory is shown in Table 6.1. 
Refer to Section 3.5.2 for details of each item. 
 
Table 6.1 Parameter setting items 
 
Setting item 
Description 
Buffer memory 
address 
Reference 
Number of connected modules 
Sets the number of modules in the remote and local stations 
connected to the master station (including reserved stations) 
Default 
: 64 (modules) 
Setting range  : 1 to 64 (modules) 
1
H
 
Section 3.5.2 (1) 
(a) 
Number of retries 
Sets the number of retries when there is a communication error. 
Default 
: 3 (times) 
Setting range  : 1 to 7 (times) 
2
H
 
Section 3.5.2 (1) 
(b) 
Number of automatic return 
modules 
Sets the number of remote and local stations that can be 
recovered with one link scan. 
Default 
: 1 (modules) 
Setting range  : 1 to 10 (modules) 
3
H
 
Section 3.5.2 (1) 
(c) 
Operation specification when 
CPU is down 
Specifies the data-link status when the master station 
programmable controller CPU has an error. 
Default 
: 0 (stop) 
Setting range  : 0 (stop) 
 
  1 (continue) 
6
H
 
Section 3.5.2 (1) 
(d) 
Reserved station specification 
Specifies reserved stations. 
Default 
: 0 (no setting) 
Setting range  : Turn on the bit corresponding to the station 
number. 
10
H
 to 13
H
 
Section 3.5.2 (1) 
(e) 
Invalid station specification 
Specifies invalid stations. 
Default 
: 0 (no setting) 
Setting range  : Turn on the bit corresponding to the station 
number. 
14
H
 to 17
H
 
Section 3.5.2 (1) 
(f) 
Station information 
Sets the connected remote and local station type. 
Default : 
0101
H
 (remote I/O station, occupies 1 station, 
station No. 1) to 0140
H
 (remote I/O station, 
occupies 1 station, station No. 64) 
Setting range  : As follows. 
Station type
Number of 
occupied stations
b15    to    b12 b11     to     b8
Station number
b7               to               b0
1 to 64
(01
H
 
to
 
40
H
)
1: Occupies 1 station 
2: Occupies 2 stations 
3: Occupies 3 stations 
4: Occupies 4 stations
0: Remote I/O station 
1: Remote device station 
2: Intelligent device station (including local stations)
 
20
H
 (1st station) to 
5F
H
 (64th station) 
Section 3.5.2 (1) 
(g)