7   DATA LINK PROCEDURE 
MELSEC-QnA 
 
7.7.4 Condition setting 
The setting method of the condition setting switch (DIP switch) is shown in Table 7.2. 
 
Table 7.2 Condition setting 
 
Setting 
Number Description 
Switch status 
Master station 
Local station 
SW1 Station 
type 
OFF : Master/local station 
ON   : Standby master station 
OFF (station number 0) 
OFF (station number 1 to 64) 
SW2 (Unusable) 
– 
Always 
OFF 
SW3 (Unusable) 
– 
Always 
OFF 
OFF
When setting all input data from the data-link faulty station to all off. (Refer 
to Section 4.9.) 
SW4 
Input data 
status of the 
data link 
faulty 
station 
OFF : Clear 
ON   : Hold 
ON
When keeping the input data from the data-link faulty station in the status 
right before the error. (Refer to Section 4.9.) 
Number of 
occupied 
stations 
SW5 SW6 
– 
1 station 
OFF 
OFF 
• Remote input RX : 32 points 
• Remote output RY : 32 points 
• Remote register RWw : 4 points 
• Remote register RWr : 4 points 
2 stations  OFF ON 
• Remote input RX : 64 points 
• Remote output RY : 64 points 
• Remote register RWw : 8 points 
• Remote register RWr : 8 points 
3 stations  ON ON 
• Remote input RX : 96 points 
• Remote output RY : 96 points 
• Remote register RWw : 12 points 
• Remote register RWr : 12 points 
SW5 
SW6 
Number of 
occupied 
stations 
4 stations 
ON 
OFF 
Setting not necessary (OFF) 
• Remote input RX : 128 points 
• Remote output RY : 128 points 
• Remote register RWw : 16 points 
• Remote register RWr : 16 points 
SW7 (Unusable) 
– 
Always 
OFF 
SW8 (Unusable) 
– 
Always 
OFF 
 The AJ61QBT11 of hardware version F or later and the A1SJ61QBT11 of hardware version G or later are compatible with this setting. 
For other than the above, only SW5 is used to set the number of occupied stations. 
OFF: 1 station occupied 
ON  : 4 stations occupied 
Keep SW6 OFF as it is unusable.