1   OVERVIEW 
MELSEC-QnA 
 
(3)   Local station communication 
The data communication between programmable controller CPUs can be 
performed in N:N relationship with bit data (remote input RX and remote output 
RY) and word data (remote register) 
 
Master station
Remote input (RX)
Remote output (RY)
Remote register (RWw)
Remote register (RWr)
Local station
Remote output (RY)
Remote input (RX)
Remote register (RWr)
Remote register (RWw)
Local station
Remote output (RY)
Remote input (RX)
Remote register (RWr)
Remote register (RWw)
Link scan
Link scan
Link scan
Link scan
Link scan
Link scan
Link scan
Link scan
 
 
(4)   Establishing high-speed transmission 
When the transmission speed of 10Mbps is set, the link scan time 
(communication time with the master station and remote station/local station) is 
still at high speed, even when the maximum 64 stations are connected. 
• Remote I/O (RX, RY) 2048 points ..................................................... 4 ms 
• Remote I/O (RX, RY) 2048 points 
+ remote register (RWw, RWr) 512 points ................ 7 ms 
 
(5)   System configurations are possible, according to requirements. 
 
(a)   Transmission distance 
The total extended distance depends on the transmission speed, but 
connections can be made between 100 m (at 10 Mbps) and 1.2 km (at 156 
kbps). 
 
(b)   Number of connected stations 
A maximum of 64 stations, including remote I/O stations, remote device 
stations, and local stations can be connected to one master station. 
Up to 64 remote I/O stations, 42 remote device stations, and 26 local 
stations can be connected. (Refer to Section 2.1.)