13 - 2 
MELSEC-QnA 
13   TROUBLESHOOTING 
 
Trouble description 
Details to be checked 
Confirmation action 
Is the remote device station performing data 
link? 
Verify using the following means: 
• LED display of the module 
• Other station data link status (SW0080 to SW0083) 
of the master station 
Is the refresh instruction (Yn0) turned on at 
the master station? 
Verify the sequence program. 
Is data written to the correct address of 
remote output RY (buffer memory)? 
Verify the sequence program. 
Is the station incorrectly set as reserved? 
Verify parameters. 
Cannot turn on/off remote output (RY) 
from a remote device station. 
Did the station number overlap? 
Verify the station number. 
Is the remote device station performing data 
link? 
Verify using the following means: 
• LED display of the module 
• Other station data link status (SW0080 to SW0083) 
of the master station 
Is data read from the correct address of the 
remote register RWr (buffer memory)? 
Verify the sequence program. 
 
Is the station incorrectly set as reserved? 
Verify the parameters. 
Unable to get the remote register 
(RWr) data from a remote device 
station. 
Did the station number overlap? 
Verify the station number. 
Is the remote device station performing data 
link? 
Verify using the following means: 
• LED display of the module 
• Other station data link status (SW0080 to SW0083) 
of the master station 
Is data written to the correct address of 
remote register RWw (buffer memory)? 
Verify the sequence program. 
Is the station incorrectly set as reserved? 
Verify the parameters. 
Unable to write data onto the remote 
register (RWw) at a remote device 
station. 
Did the station number overlap? 
Verify the station number. 
Is the corresponding local station performing 
data link? 
Check the LED indication of the corresponding local 
station. 
 Check Other station data link status (SW0080 to 
SW0083) of the master station. 
Is the refresh instruction (Yn0) at the master 
station turned on? 
Verify the sequence program. 
Is data written to the correct address of the 
remote output RY (buffer memory) at the 
master station? 
Verify the sequence program. 
Is data read from the correct address of the 
remote input RX (buffer memory) at the local 
station? 
Verify the sequence program. 
Is the station incorrectly set as reserved? 
Verify the parameters. 
Unable to communicate from the 
master station (remote output RY) to 
the local station (remote input RX). 
Did the station number overlap? 
Verify the station number. 
Is the corresponding local station performing 
data link? 
Check the LED indication of the corresponding local 
station. 
 Check Other station data link status (SW0080 to 
SW0083) of the master station. 
Is the refresh instruction (Yn0) at the local 
station turned on? 
Verify the sequence program. 
Is data written to the correct address of 
remote output RY (buffer memory) at the 
local station? 
Verify the sequence program. 
Is data read from the correct address of the 
remote input RX (buffer memory) at the 
master station? 
Verify the sequence program. 
Is the station incorrectly set as reserved? 
Verify the parameters. 
Unable to communicate from the local 
station (remote output RY) to the 
master station (remote input RX). 
Did the station number overlap? 
Verify the station number.