15   FUNCTIONS (FUNCTION VERSION B OR LATER) 
 
15.2.1 Network parameters 
Network parameters are used for performing data link. The items that are set by the 
network parameters are shown in Table 15.2. 
 
Table 15.2 Network parameters 
Buffer memory address 
Setting item 
Description 
Hex. Dec. 
Number of connected 
modules 
Sets the number of remote stations, local stations, intelligent device 
stations, and standby master station connected to the master station. 
(Includes reserved stations.) 
Default value : 64 (modules) 
Setting range : 1 to 64 (modules) 
1
H
 1 
Number of retries 
Sets the number of retries during the communication error. 
Default value : 3 (times) 
Setting range : 1 to 7 (times) 
2
H
 2 
Number of automatic return 
modules 
Sets the number of remote stations, local stations, intelligent device 
stations, and standby master station that can be returned by one 
link scan. 
Default value : 1 (module) 
Setting range : 1 to 10 (modules) 
3
H
 3 
Standby master station 
specification 
Specifies the station number of the standby master station. 
Default value : 0 (0: No standby master station specified.) 
Setting range : 0 to 63 (0: No standby master station specified.) 
4
H
 4 
Operation specification 
when CPU becomes faulty 
Specifies the data link status when a master station programmable 
controller CPU error occurs. 
Default value : 0 (stop) 
Setting range : 0 (stop) 
 
  1 (continue) 
6
H
 6 
Scan mode specification 
Specifies the synchronous or asynchronous mode for sequence scan. 
Default value : 0 (asynchronous) 
Setting range : 0 (asynchronous) 
 
  1 (synchronous) 
– – 
Delay time setting 
Set 0 for the delay time. 
8
H
 8 
Reserved station 
specification 
Specifies the reserved station. 
Default value : 0 (Not set) 
Setting range : Turn on the bit corresponding to the station number.
10
H
 to 13
H
 
16 to 19 
Error invalid station 
specification 
Specifies the error invalid station. 
Default value : 0 (Not set) 
Setting range : Turn on the bit corresponding to the station number.
14
H
 to 17
H
 
20 to 23 
Station information 
Sets the type of the connected remote stations, local stations, 
intelligent device station, and standby master station. 
Default value : 0101
H
 (remote I/O station, 1 station occupied, station 
number 1) to  
0140
H
 (remote I/O station, 1 station occupied, 
station number 64) 
Setting range : See below. 
 
Station type
b15
b8
to
to
b7
to
b0
Occupied
stations
Station No.
1 : 1 station occupied  
2 : 2 stations occupied  
3 : 3 stations occupied  
4 : 4 stations occupied
1 to 64  
(01
H
 to 40
H
)
b12 b11
0 : Remote I/O station  
1 : Remote device station  
2 : Intelligent device station
     (Local station and standby
     master station are included)
 
 
20
H
 (first module)  
to  
5F
H
 (64th module) 
32 (first module) 
to  
95 (64th module)