15 - 8 
MELSEC-QnA 
15   FUNCTIONS (FUNCTION VERSION B OR LATER) 
 
15.5.3 Link special relays/registers (SB, SW) relating to the standby master function 
The link special relays and link special registers relating to the standby master function 
are explained. 
They are stored in the buffer memory. 
 
(1)   Link special relays (SB) 
The link special relays (SB) relating to the standby master function are as follows. 
The figures in parentheses in the number column indicate buffer memory 
address and bit location. 
 
Example: When buffer memory address is 5E0
H
 and bit location is 0: (5E0
H
, b0) 
 
Table 15.4 List of link special relays relating to the standby master function 
 
Availability  
(  : available,   : not available) 
Number Name 
Description 
Master station 
Standby master 
station 
SB0001 
(5E0
H
, b1) 
Master station switch data 
link start 
Switches the output information from the standby master 
station to the master station to start the data link. 
OFF  : No request 
ON : 
Request 
 
 
SB0042 
(5E4
H
, b2) 
Master station switch data 
link start acceptance 
status 
Indicates the acceptance status specified for switching data 
link start from the standby master station to the master station.
OFF  : Not accepted 
ON : 
Accepted 
 
 
SB0043 
(5E4
H
, b3) 
Master station switch data 
link start complete status 
Indicates the acceptance complete status specified for 
switching data link start from the standby master station to the 
master station. 
OFF  : Not completed 
ON : 
Completed 
 
 
SB0070 
(5E7
H
, b0) 
Master station data link 
status 
Indicates the data link status. 
OFF  : Data link by the master station 
ON  : Data link by the standby master station 
 
 
SB0071 
(5E7
H
, b1) 
Standby master station 
information 
Indicates whether there is standby master station or not. 
OFF : No 
ON : 
Yes 
 
 
 
(2)   Link special registers (SW) 
The link special registers (SW) relating to the standby master function are as 
follows. 
The figures in parentheses in the number column indicate buffer memory 
address. 
 
Table 15.5 List of link special registers relating to the standby master function 
 
Availability  
(  : available,   : not available) 
Number Name 
Description 
Master station 
Standby master 
station 
SW0043 
(643
H
Master station switch data 
link start result 
Stores the results of execution of the master station switch 
data link start instruction by SB0001. 
0 : 
Normal 
Other than 0  : Stores error code (Refer to Section 13.3) 
 
 
SW0073  
(673
H
Standby master station 
number 
Stores the standby master station number. 
1 to 63 (stations)