Справочник Пользователя для Mitsubishi Electronics A1SJ61QBT11

Скачать
Страница из 294
 
 
 
3 - 2 
3   SPECIFICATION 
MELSEC-QnA 
 
3.2 Performance Specifications 
The performance specifications of the CC-Link is shown in Table 3.2. 
 
Table 3.2 Performance specifications 
 
Item AJ61QBT11 
A1SJ61QBT11 
Transmission speed 
Can select from 156 kbps/ 625 kbps/ 2.5 Mbps/ 5 Mbps/ 10 Mbps 
Maximum overall cable distance 
(Maximum transmission distance) 
Different from the transmission speed: (Refer to Section 3.2.1, 3.2.2) 
Maximum number of connected modules  
(when master station) 
64 modules 
However, the following conditions must be satisfied:  
{(1×a) + (2×b) + (3×c) + (4×d)}   64 
a: number of modules occupying 1 station 
b: number of modules occupying 2 stations 
c: number of modules occupying 3 stations 
d: number of modules occupying 4 stations 
 
{(16×A) + (54×B) + (88×C)}   2304 
A: Number of remote I/O stations   64 
B: Number of remote device stations   42 
C: Number of local stations,  
standby master stations,  
intelligent device stations   26 
Number of occupied stations  
(when local station) 
1 to 4 stations 1 (switched using DIP switch) 
Maximum link points for one system 
Remote I/O (RX, RY) 
: 2048 points 
Remote register (RWw)  : 256 points (master station   remote/local station) 
Remote register (RWr)  : 256 points (remote/local station   master station) 
Link points for one remote/local station 
Remote I/O (RX, RY) 
: 32 points (local station: 30 points) 
Remote register (RWw)  : 4 points (master station   remote/local station) 
Remote register (RWr)  : 4 points (remote/local station   master station) 
Communication method 
Broadcast polling method 
Synchronous method 
Frame synchronous method 
Encoding method 
NRZI method 
Transmission path 
Bus (RS-485) 
Transmission format 
HDLC standard 
Error control system 
CRC (X
16
 + X
12
 + X
5
 + 1) 
Connection cable 2 
CC-Link dedicated cable (Ver.1.00)/CC-Link dedicated high performance cable/Version 
1.10 compatible CC-Link dedicated cable 
RAS function 
• Automatic return function 
• Slave station cutoff function 
• Error detection by the link special relay/register 
Number of parameter registration to E
2
PROM  10,000 times 
I/O occupied points 
32 points (I/O allocation: 32 special points) 
Internal current consumption (5VDC) 
0.45 A 
0.4 A 
Weight 
0.4 kg 
0.25 kg 
1: The AJ61QBT11 of hardware version F or later and the A1SJ61QBT11 of hardware version G or later are compatible with this setting. 
For other than the above, the setting is 1 or 4 stations only. 
2: Each of Ver.1.10 compatible CC-Link cables, CC-Link dedicated cables (Ver.1.00), and CC-Link dedicated high performance cables 
must not be used together with other cable types.   
If different cable types are used together, normal data transmission is not guaranteed. 
Also attach the terminating resistor which matches the kind of the cable. (Refer to section 7.5)