Справочник Пользователя для Mitsubishi Electronics FX3S-MT/ES

Скачать
Страница из 216
34
FX
3S
 Series Programmable Controllers
User's Manual - Hardware Edition
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.5 Performance Specifications
4.5
Performance Specifications
The performance specifications for the main unit are explained below.
Item
Performance
Operation control system
Stored program repetitive operation system with interruption function.
Input/output control system
Batch processing system (when END instruction is executed)
Input/output refresh instruction and pulse catch function are provided.
Programming language
Relay symbol system + step-ladder system (SFC notation possible)
Program memory
Built-in memory capacity/type
16,000 steps/EEPROM memory (Program capacity is 4000 steps.)
Max. allowable write: 20,000 times
Memory cassette (Option)
32,000 steps/EEPROM memory (with loader function)
The FX
3S
 Series PLC is available only to 16,000 steps. (Program capacity is 4000
steps.)
Max. allowable write: 10,000 times
Writing function during running
Provided (Program can be modified while the PLC is running.)

For the writing function during running, refer to Subsection 5.2.5
.
Keyword function
With keyword/Customer keyword function
Real-time clock
Clock function
*1
Built-in
1980 to 2079 (with correction for leap year)
2- or 4-digit year, accuracy within 45 seconds/month at 25 °C
Kinds of instructions
Basic instructions
Sequence instructions: 29
Step-ladder instructions: 2
Applied instructions
116 kinds
Processing speed
Basic instructions
0.21
s/instruction
Applied instructions
0.5 
s to several hundred s/instruction
Number of input/
output points
Input points
16 points or less (Extension is impossible.)
Output points
14 points or less (Extension is impossible.)
Input/output relay
Input relay
X000 to X017
The device numbers are octal.
Output relay
Y000 to Y015
Auxiliary relay
For general
M0 to M383
384 points
EEPROM keep
M384 to M511
128 points
For general
M512 to M1535
1024 points
For special
M8000 to M8511
512 points
State
For initial state 
(EEPROM keep)
S0 to S9
10 points
EEPROM keep
S10 to S127
118 points
For general
S128 to S255
128 points
Timer 
(on-delay timer)
100 ms
T0 to T31
32 points
0.1 to 3,276.7 sec
100 ms/10 ms
T32 to T62
31 points
0.1 to 3,276.7 sec/0.01 to 327.67 sec
When M8028 is driven ON, timers T32 to
T62 (31 points) are changed to 10 ms
resolution.
1 ms
T63 to T127
65 points
0.001 to 32.767 sec
1 ms accumulating type
T128 to T131
4 points
0.001 to 32.767 sec
100 ms accumulating type
T132 to T137
6 points
0.1 to 3,276.7 sec
Variable analog potentiometers
Available as analog timers
VR1: D8030
VR2: D8031
For compatible PLCs, refer to Chapter 11.
Analog inputs
Available as voltage inputs
ch1: D8270
ch2: D8271
For compatible PLCs, refer to Chapter 11.
Counter
16 bits up (For general)
C0 to C15
16 points
Counting from 0 to 32,767
16 bits up (EEPROM keep)
C16 to C31
16 points
Counting from 0 to 32,767
32 bits up/down (For general)
C200 to C234
35 points
Counting from -2,147,483,648 to
+2,147,483,647