Справочник Пользователя для Mitsubishi Electronics A1SJ61BT11

Скачать
Страница из 294
 
 
 
5 - 13 
5   DATA LINK PROCESSING TIME 
MELSEC-QnA 
 
(3)   Master station (RWw)   local station (RWr) 
[Expression] 
SM + LS × 3 + SL [ms] 
 
  SM : Scan time of the master station's sequence program 
  LS  : Link scan time (See Section 5.2.) 
  SL  : Scan time of the local station's sequence program 
 
[Data flow] 
Programmable controller CPU
(SM)
Link scan (LS)
Master station buffer memory 
(Remote register RWw) 
Local station buffer memory 
(Remote register RWr)
Programmable controller CPU
(SL)
FROM
FROM
TO
TO