7   DATA LINK PROCEDURE 
MELSEC-QnA 
 
Item Specification 
Remarks 
CC-Link dedicated cable, Version 1.10 compatible CC-Link dedicated cable (terminating resistor 110 
Ω) 
Transmission 
speed 
Maximum length of 
main line 
Distance 
between 
branches
Length of cable between 
the remote I/O stations or 
remote device stations 1 
Length of cable between the 
master/local station or intelligent 
device station and the adjacent 
station (s)  2 
625 kbps 
100 m (328.1 ft.) 
Maximum length of main line, 
distance between T branches, and 
length of cable between stations 
156 kbps 
500 m (1640.5 ft.) 
No limit 
30 cm (11.8 in.) or longer 
1 m (3.28 ft.) or longer ( 3)/ 
2 m (6.56 ft.) or longer ( 4) 
3: The cable length of 1 m (3.28 ft.) or longer is for a system configured only with remote I/O stations and remote device stations. 
4: The cable length of 2 m (6.56 ft.) or longer is for a system configuration that contains local stations and intelligent device stations. 
 
Master station
Terminating
resistor
Terminating
resistor
R
R
R
R
R
L/I
L/I
L/I
L/I
R
R
R
R
R
L/I
R
(Length of branch line: 8m (26.25 ft.) or shorter)
: Indicates a remote I/O station or a remote device station.
: Indicates a local station or an intelligent device station.
1
1
1
1
2
2
R
2
2
1
1
2
2
2
2
1
1
Distance between T branches
Maximum length of main line (not including branch line length)
(Length of branch line: 8m (26.25 ft.) or shorter)
2
R
R