Справочник Пользователя для Mitsubishi Electronics A1SJ61BT11

Скачать
Страница из 294
 
 
 
1 - 10 
1   OVERVIEW 
MELSEC-QnA 
 
1.3.2 Communication between the master station and remote device station 
The overview of the communication between the master station and remote device 
station is described below. 
Refer to Section 4.3 for details. 
 
SET Yn0
SET Yn6
1
2
FROM
4
Refresh instruction
Data-link startup
Remote input 
(RX)
Buffer memory
Link scan
Programmable controller CPU
Master station
Remote device station
Remote input 
(RX)
3
TO
5
Remote output 
(RY)
Link scan
Remote output 
(RY)
6
TO
7
Remote register 
(RWw)
Link scan
Remote register 
(RWw)
8
FROM
10
Remote register 
(RWr)
Link scan
9
Remote register 
(RWr)
 
 
1
 Turn on the refresh instruction. 
2
 Startup the data link. 
3
 By the link scan, the remote device station's remote input (RX) is stored in the 
master station's remote input (RX). 
4
 By the FROM instruction, read data from the remote input (RX). 
5
 By the TO instruction, write data to the remote output (RY). 
6
 By the link scan, the remote device station's remote output (RY) is turned on/off. 
7
 By the TO instruction, write data to the remote register (RWw). 
8
 By the link scan, the data is sent to the remote device station's remote register 
(RWw). 
9
 By the link scan, the remote device station's remote register (RWr) is sent to the 
master station's remote register (RWr). 
10
 By the TO instruction, read data from the remote register (RWr).