15   FUNCTIONS (FUNCTION VERSION B OR LATER) 
 
15.4 Scan Synchronous Function 
This function sets whether link scan is synchronized with the sequence scan, using the 
network parameter setting. 
 
15.4.1 Synchronous mode 
Performs data link using the scan synchronized with the sequence program. The 
operation overview in the synchronous mode is shown in Figure 15.1. 
In general, the transmission delay is smaller in the synchronous mode than in the 
asynchronous mode. 
Select the synchronous mode if the transmission delay is noticeably long. 
However, as sequence scan is synchronized with link scan in the synchronous mode, 
the link scan is prolonged if the sequence scan is long. In this case, select the 
asynchronous mode. 
 
Important 
 
While in the synchronous mode, the scan time must not exceed the time specified for the 
corresponding transmission speed, as shown below. If the specified time is exceeded, a time 
out error occurs at each station and the station becomes faulty. 
 
Transmission speed 
Scan time 
 
 
10Mbps 50ms 
 
 
5Mbps 50ms 
 
 
2.5Mbps 100ms 
 
 
625kbps 400ms 
 
 
156kbps 800ms 
 
 
1
 Sequence scan > link scan 
END
END
END
END
Send
LS : Link scan
SM : Sequence scan
Receive
Send
Send
Send
Output transmission
delay (SM + LS)
Input transmission delay
(SM + LS  2)
Receive
Receive
Receive
 
 
2
 Sequence scan < link scan 
Output transmission
delay (SM + LS)
END
END
END
END
END
END
END
END
END
Link scan
Sequence
scan
Input transmission delay
(SM + LS  2)
Send
Send
Send
Send
Send
Send
Send
Send
Send
Receive
Receive
Receive
Receive
 
 
Figure 15.1 Operation overview in the synchronous mode