Справочник Пользователя для Mitsubishi Electronics A1SJ61BT11

Скачать
Страница из 294
 
 
 
3 - 7 
3   SPECIFICATION 
MELSEC-QnA 
 
3.4 I/O Signals to the Programmable Controller CPU 
The I/O signals for the master/local module's programmable controller CPU is 
described. 
 
3.4.1 I/O signal list 
The list of I/O signals is described in Table 3.3. 
The "n" in the table indicates the master/local module's first I/O number, and it is 
determined by the installation position and the module installed before the master/local 
module. 
<Example> When the master/local module's first I/O number is "X/Y30": 
Xn0 to X(n+1)F   X30 to X4F 
Yn0 to Y(n+1)F   Y30 to Y4F 
 
Table 3.3 I/O signal list 
 
Signal direction: programmable controller CPU   master/local module Signal direction: programmable controller CPU   master/local module
Availability Availability 
Input 
number 
Signal name 
Master 
station 
Local 
station 
Output 
number 
Signal name 
Master 
station 
Local 
station 
Xn0 Module 
error 
 
 
Yn0 Refresh 
instruction 
 
 
Xn1 
Data link status at host station 
 
 
Yn1 
Xn2 Parameter 
setting 
status 
 
 
Yn2 
Xn3 
Data link status at other stations 
 
 
Yn3 
(Prohibited to use) 
– 
– 
Xn4 
Module reset acceptance complete 
 
 
Yn4 
Module reset request 
 
 
Xn5 
(Prohibited to use) 
– 
– 
Yn5 
(Prohibited to use) 
– 
– 
Xn6 
Data link startup by buffer memory 
parameter normal completion 
 
 
Yn6 
Data link startup request from buffer 
memory parameters 
 
 
Xn7 
Data link startup by buffer memory 
parameter error completion 
 
 
Yn7 
(Prohibited to use) 
– 
– 
Xn8 
Data link startup by E
2
PROM 
parameter normal completion 
 
 
Yn8 
Data link startup request from the 
E
2
PROM parameters 
 
 
Xn9 
Data link startup by E
2
PROM 
parameter error completion 
 
 
Yn9 
(Prohibited to use) 
– 
– 
XnA 
Parameter registration to E
2
PROM 
normal completion 
 
 
YnA 
Parameter registration request to 
E
2
PROM 
 
 
XnB 
Parameter registration to E
2
PROM 
error completion 
 
 
YnB 
XnC 
(Prohibited to use) 
– 
– 
YnC 
(Prohibited to use) 
– 
– 
XnD 
E
2
PROM erasure normal completion 
 
 
YnD 
E
2
PROM erasure request 
 
 
XnE 
E
2
PROM erasure abnormal 
completion 
 
 
YnE 
XnF Module 
ready 
 
 
YnF 
(Prohibited to use) 
– 
– 
: Usable    : Prohibited to use