3.5.2 Buffer memory details 
The details of each item shown in Table 3.4 of Section 3.5.1 is described. 
 
(1)   Parameter information area 
The conditions to perform data link is set.  
Also, these can be registered in the E
2
PROM. 
 
Table 3.5 Parameter information area list 
 
Address 
Hex. Dec. 
Item Description Default 
0
H
 
(Prohibited to use)   – 
– 
1
H
 1 
Number of connected 
modules 
Set the number of connected remote/local station modules. 
(including reserved stations) 
64 
2
H
 
Number of retries 
Set the number of retries to the communication faulty station. 
3
H
 3 
Number of automatic 
return modules 
Set the number of remote/local stations modules that can 
return with 1 link scan. 
4
H
 
(Prohibited to use)   – 
– 
5
H
 
(Prohibited to use)   – 
– 
6
H
 6 
Operation specification 
when CPU is down 
Specify the data-link status when there is a master station 
programmable controller CPU error. 
0 (Stop) 
7
H
 to F
H
 
7 to 15 
(Prohibited to use)   – 
– 
10
H
 to 13
H
  16 to 19 
Reserved station 
specification 
Set a reserved station. 
0 (No specification) 
14
H
 to 17
H
  20 to 23 
Invalid station 
specification 
Specify an invalid station. 
0 (No specification) 
18
H
 to 1F
H
  24 to 31 
(Prohibited to use)   – 
– 
20
H
 to 5F
H
  32 to 95  Station information 
Set the connected remote/local station type. 
Station type: Remote I/O 
station 
Number of occupied 
stations: 1 
Station numbers: 1 to 64 
 Do not write to areas that are prohibited to use. An error may occur. 
 
(a)   Number of connected modules 
This sets the number of remote/local station modules connected to the 
master station (including reserved stations). 
This is not a station count. 
The setting range is "1 to 64 (modules)." 
 
POINT 
 
The station information (address 20
H
 to 5F
H
) for the specified "number of connected" stations 
becomes valid. 
 
(b)   Number of retries 
This sets the number of retries to the remote/local station with a data link 
error. 
The setting range is "1 to 7 (times)." 
If the remote/local station cannot recover a normal data link after 
performing specified number of retries, the station becomes a "data-link 
faulty station."