Справочник Пользователя для Mitsubishi Electronics FX3S-MR/ES

Скачать
Страница из 216
32
FX
3S
 Series Programmable Controllers
User's Manual - Hardware Edition
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.4 Output Specifications
4.4
Output Specifications
The output specifications for the main unit are explained below.
4.4.1
Relay output specifications
Item
Relay output specification
FX
3S
-10MR
FX
3S
-14MR
FX
3S
-20MR
FX
3S
-30MR
Number of output points
4 points
6 points
8 points
14 points
Output connecting type
Fixed terminal block (M3 screw)
Output form
Relay
External power supply
30 V DC or less, 
240 V AC or less (250 V AC or less when the unit does not comply with CE, UL or cUL standards.)
Max. load
Resistance load
2 A/point
The total load current of resistance loads per common terminal should be the following value.
For details on the common terminal for each model, refer to the Section 4.7.
1 output point/common terminal: 2 A or less
4 output points/common terminal: 8 A or less
Inductive load
80 VA (UL and cUL standards approved at 120 and 240 V AC.)
For the product life, refer to Subsection 14.4.2.
For cautions on external wiring, refer to Subsection 12.1.3.
Min. load
5 V DC, 2 mA (reference value)
Open circuit leakage current
-
Response time
OFF
ON
ON
OFF
Approx. 10 ms
Output circuit insulation
Mechanical insulation
Output operation display
LED on panel lights when power is applied to relay coil.
Output circuit configuration
Load
Y
Fuse
AC power
supply
COM
Load
Y
Fuse
DC power
supply
COM
A common number applies to the     of [COM     ].