Appendix 7 - 2
Appendix 7 Higher Harmonic Suppression Measure Guidelines
MITSUBISHI CNC
Appendix 7-1 Higher harmonic suppression measure guidelines
These guidelines apply to users for which the 6-pulse equivalent capacity total of the installed higher 
harmonic generator exceeds the reference in the following table. (Note that household appliances and 
general-purpose products having a rated current of 20A/phase or less connected to a 300V or less 
commercial power supply are excluded from the generators.)
Use the following flow chart to confirm whether the total exceeds the reference.
Higher Harmonic Suppression Guidelines were set in September 1994 by the Ministry of International Trade 
and Industry's Agency of Natural Resources and Energy.
Higher Harmonic Suppression Measure Guidelines for Household Appliances and General-purpose 
Products
Higher Harmonic Suppression Measure Guidelines for Consumers Receiving High Voltage or Special 
High Voltage Power
Higher harmonic 
suppression measures 
required
 
New installation, expansion or upgrading of facility
 
Calculation of total equivalent capacity
 
Calculation of higher harmonic current flow
 
Higher harmonic suppression measures not required
 
Higher harmonic current 
Step 2
 
Total equivalent capacity 
Step 1
 
Reference capacity exceeded 
Reference capacity or less
 
Upper limit value exceeded 
Upper limit