10.4 Allocation of Device Numbers to Input Numbers
10.4
Allocation of Device Numbers to Input Numbers
The high-speed counter numbers are allocated to the input terminals X000 to X007 as shown in the following
table. The input terminals not allocated for high-speed counters can be used as general input terminals.
10.4.1 Allocation table
U: Up-count input
D: Down-count input
A: A-phase input
B: B-phase input
R: External reset input
S: External start input
*1.
When a special auxiliary relay is driven in a program, the input terminals and their associated
functions are switched.
For the function switching method, refer to Subsection 10.9.2.
10.4.2 Restriction of redundant use of input numbers
The input terminals X000 to X007 can be used for high-speed counters, input interruption, pulse catch, SPD
instruction, ZRN instruction and DSZR instruction and general-purpose inputs. 
Take care not to overlap the input numbers.
High-speed counter type
High-speed counter No.
Input allocation
X000
X001
X002
X003
X004
X005
X006
X007
1-phase 1-count input
C235
U/D
C236
U/D
C237
U/D
C238
U/D
C239
U/D
C240
U/D
C241
U/D
R
C242
U/D
R
C243
U/D
R
C244
U/D
R
S
C245
U/D
R
S
1-phase 2-count input
C246
U
D
C247
U
D
R
C248
U
D
R
C248 (OP)
*1
U
D
C249
U
D
R
S
C250
U
D
R
S
2-phase 2-count input
C251
A
B
C252
A
B
R
C253
A
B
R
C253 (OP)
*1
A
B
C254
A
B
R
S
C255
A
B
R
S