Справочник Пользователя для Mitsubishi Electronics FX3S-30MT/ES-2AD

Скачать
Страница из 216
12 Output Wiring Procedures
111
FX
3S
 Series Programmable Controllers
User's Manual - Hardware Edition
11
Bui
lt-
in Anal
og
12
O
utpu
t Wi
ring
13
Wiri
ng for
Va
rious U
ses
14
Te
st R
un,
M
ain
tenanc
e,
Troub
le
shooting
15
Oth
er Ex
tensi
on
U
nit
s and
Opti
ons
16
Displ
ay
 Modul
(FX
3S
-5
D
M
)
17
Me
m
ory
C
ass
ette
A
Spec
ial D
evices 
(M
8000-,
 D8000-)
B
Instruc
tion Li
st
C
Di
sc
onti
nued
model
s
12.1 External Wiring for Relay Output Type
12.1.3 External wiring precautions
1. Protection circuit for load short-circuiting
A short-circuit at a load connected to an output terminal
could cause burnout at the output element or the PCB. To
prevent this, a protection fuse should be inserted at the
output.
2. Contact protection circuit for inductive loads
An internal protection circuit for the relays is not provided for the relay output circuit in this product. It is
recommended to use inductive loads with built-in protection circuits. When using loads without built-in
protection circuits, insert an external contact protection circuit, etc. to reduce noise and extend the product
life.
1) DC circuit
Connect a diode in parallel with the load.
The diode (for commutation) must comply with the
following specifications.
2) AC circuit
Connect the surge absorber (combined CR components
such as a surge killer and spark killer, etc.) parallel to
the load. Select the rated voltage of a surge absorber
that is suitable for the load being used. Refer to the
table below for other specifications.
Reference
3. Interlock
For loads such as forward/reverse contactors, etc., where a
hazardous condition could result if switched ON
simultaneously, an external interlock should be provided for
interlocking the PLC’s internal programs as shown to the
right.
4. In-phase
PLC output contacts (*) should be used in an "in-phase"
manner.
Item
Guide
Reverse voltage
5 to 10 times the load voltage
Forward current
Load current or more
Item
Guide
Static electricity capacity
Approx. 0.1 
F
Resistance value
Approx. 100 to 200 
Manufacturer
Model name
Manufacturer
Model name
Okaya Electric Industries Co., Ltd. CR-10201
Rubycon Corporation
250MCRA104100M B0325
Load
Fuse
Y001
COM1
Main unit
+
-
Inductive load
PLC output
contact
Diode
(for commutation)
Inductive load
PLC output
contact
Surge
absorber
Interlock
PLC output
contact
PLC output
contact
Limit of
normal 
rotation
Limit of
reverse
rotation
Normal 
rotation
Reverse 
rotation
*
*
*
*
Bad
Good