Справочник Пользователя для Mitsubishi Electronics FX3S-30MT/ES-2AD

Скачать
Страница из 216
9 Input Wiring Procedures
9.2 24 V DC input (Sink and source input type)
80
FX
3S
 Series Programmable Controllers
User's Manual - Hardware Edition
9.2.3
Examples of external wiring [AC power type]
1. Sink input
2. Source input
*1.
Handle the power supply circuit correctly in accordance with Chapter 8 "Preparation for Wiring and
Power Supply Wiring Procedures."
*2.
For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance
may be required.
*3.
In the case of sink input wiring, short-circuit the [S/S] terminal and the [24V] terminal of the main unit.
In the case of source input wiring, short-circuit the [S/S] terminal and the [0V] terminal of the main unit.
*4.
The "0V" and "24V" terminals are located on the output terminal side. 
For details on the terminal layout, refer to Section 4.7.
X0
S/S
0V
24V
N
L
X2
X1
Main unit
Fuse
Class D 
grounding
Input 
impedance
Input 
terminal
Three-wire 
sensor
*1
*3
*2
Two-wire 
proximity sensor
*4
*4
0 V
24 V
Main unit
Fuse
Class D 
grounding
Input 
impedance
Input 
terminal
Three-wire 
sensor
*1
*3
*2
Two-wire 
proximity sensor
*4
*4
0 V
24 V
X0
S/S
0V
24V
N
L
X2
X1