Справочник Пользователя для Mitsubishi Electronics AJ65bt-r2

Скачать
Страница из 264
3 - 1
MELSEC-A
3   SPECIFICATIONS
   3
3. SPECIFICATIONS
3.1 General specifications
The general specifications of the R2 are shown below.
Item
Specifications
Working ambient
temperature
0 to 55°C
Storage ambient
temperature
-20 to 75°C
Working ambient humidity
10 to 90%RH, with no dew condensation
Storage ambient humidity
10 to 90%RH, with no dew condensation
Frequency
Acceleration
Amplitude
No. of sweeps
10 to 57Hz
0.075mm
When there is
intermittent
vibration
57 to 150Hz
9.8m/s
2
10 to 57Hz
0.035mm
Vibration resistance
JIS B 3502,
IEC 61131-2
compliant
When there is
continuous
vibration
57 to 150Hz
4.9m/s
2
10 times each in
X, Y and Z
directions
(for 80 minutes)
Impact resistance
JIS B 3502, IEC 61131-2 compliant (147m/s
2
, 3 times each in X, Y and Z directions)
Working atmosphere
No corrosive gases
Working altitude  *
3
2000m or less
Installation place
Inside control panel
Overvoltage category  *
1
II or less
Degree of contamination
*
2
2 or less
*1 Indicates to which power distribution section, from the public power distribution network to the in-plant
machine device, the device is assumed to be connected.
Category II applies to a device fed power from a fixed facility.
The withstand surge voltage level for a device with a rating up to 300V is 2500V.
*2 Exponential indicating the degree of conductive matter generated in the environment where device is
used.
In the degree of contamination level 2, only non-conductive contaminants are generated. However,
temporary conductivity could occur due to rare condensation.
*3 Do not use or store the programmable controller in the environment where the pressure is higher than the
atmospheric pressure at sea level. Otherwise, malfunction may result. To use the programmable controller