Справочник Пользователя для Mitsubishi Electronics AJ65bt-r2

Скачать
Страница из 264
4 - 6
MELSEC-A
4   PROCEDURES AND SETTINGS BEFORE OPERATION
4.4 Names of each part, and settings
The names of the parts in the R2, the LED details, and the settings for each switch are
explained in this section.
(10)
(1)
(3)
(2)
(7)
(6)
(8)
(9)
(5)
(4)
No.
Name
Details
LED name
Details
PW
ON: Power is ON.
OFF: Power is OFF.
RUN
ON: Operating normally
OFF: Power (24VDC) is OFF, WDT error is occurring or
the switch setting is incorrect.
De-
fault
state
L RUN
ON: Communicating normally
OFF: Communication stopped (Time over error) or the
switch setting is incorrect.
State L ERR.
ON: Any transmission speed or station number out of range is set.
Flickering at constant intervals : The transmission speed or station number has been
changed after the power is turned on.
Flickering not constant intervals : The terminating resistor is not connected. The module or
CC-Link dedicated cable is being affected by noise.
OFF: Communicating normally
SD
ON, Flashing: Data link   Sending data
OFF: Data link   Not sending data
Others
RD
ON, Flashing: Data link   Receiving data
OFF: Data link   Not receiving data
XC, XD
ON: General-purpose input (XC, XD) is ON.
OFF: General-purpose input (XC, XD) is OFF.
YC, YD
ON: General-purpose output (YC, YD) is ON.
OFF: General-purpose output (YC, YD) is OFF.
RS-232-C SD
ON, Flashing: Sending RS-232-C data
OFF: Not sending RS-232-C data
RS-232-C RD
ON, Flashing: Receiving RS-232-C data
OFF: Not receiving RS-232-C data
RS-232-C
ERR.
ON: RS-232-C transmission error
OFF: No error
(1) Operation display LEDs