Справочник Пользователя для Mitsubishi Electronics FX0

Скачать
Страница из 382
FX Series Programmable Controlers
Applied Instructions 5
5-101
5.9.6
VRRD (FNC 85)
Operation:
The identified volume (S) on the FX-8AV is read as
an analog input. The analog data is in an 8 bit
format, i.e. values from 0 to 255 are readable. The
read data is stored at the destination device
identified under operand D.
5.9.7
VRSD (FNC 86)
Operation:
The identified volume (S) on the FX-8AV is read as
a rotary switch with 11 set positions (0 to 10). The
position data is stored at device D as an integer
from the range 0 to 10.
Mnemonic
Function 
Operands
Program steps
S
D
VRRD
FNC 85
(Volume
read)
Reads an analog
value from 1 of 8
volume inputs on
the FX-8AV
K, H
Note:
S= 0 to 7
corresponding to the 8 available
volumes on the FX-8AV
KnY, KnM, KnS
T, C, D, V, Z 
VRRD,
VRRDP:
5 steps
Mnemonic
Function 
Operands
Program steps
S
D
VRSC
FNC 86
(Volume
scale)
Reads the set
position value, 0
to 10, from
volume inputs on
the FX-8AV
K, H
Note:
S= 0 to 7
corresponding to the 8 avail-
able
volumes on the FX-8AV
KnY, KnM, KnS
T, C, D, V, Z 
VRSC,
VRSCP:
5 steps
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)
FX
(2C)
FX
FX
2N(C)
FX
0N
FX
0(s)
PULSE-P
FX
(2C)
FX
FX
2N(C)
FX
0N
FX
0(s)
16 BIT OPERATION
FX
FX
0N
FX
0(s)
FX
(2C)
FX
2N(C)
32 BIT OPERATION
X0
VRRD K 0
D 0
[ S ]
[ D ]
Note:
The FX-8AV volume ‘inputs’ are able to be read in two formats, a) as an analog value and b)
as an 11 (0 to 10) position rotary switch. The second use is described in the VRSC instruction
(FNC 86).
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)
FX
(2C)
FX
FX
2N(C)
FX
0N
FX
0(s)
PULSE-P
FX
(2C)
FX
FX
2N(C)
FX
0N
FX
0(s)
16 BIT OPERATION
FX
FX
0N
FX
0(s)
FX
(2C)
FX
2N(C)
32 BIT OPERATION
[ S ]
[ D ]
X0
VRSC K 1
D 1
Note:
The FX-8AV volume ‘inputs’ are able to be read in two formats, a) as a 11 (0 to 10) position
rotary switch and b) as an analog value. The second use is described in the 
VRRD
instruction (FNC 85).