FX Series Programmable Controllers
Devices in Detail 4
4-28
4.11.4
Availability of High Speed Counters 
on FX
2N(C)
 PLC’s
The following device table outlines the range of available high speed counters on FX
2N(C)
Key: 
U - up counter input 
D - down counter input
R - reset counter (input) 
S - start counter (input)
A - A phase counter input 
B - B phase counter input
- Counter is backed up/latched
Input assignment:
X6 and X7 are also high speed inputs, but function only as start signals. They cannot be 
used as the counted inputs for high speed counters.
Different types of counters can be used at the same time but their inputs must not 
coincide. For example, if counter C247 is used, then the following counters and 
instructions cannot be used;
C235, C236, C237, C241, C242, C244, C245, C246, C249, C251, C252, C254, I0
I1
, I2
.
Counter Speeds:
General counting frequencies:
-
Single phase and bi-directional counters; up to 10 kHz.
-
A/B phase counters; up to 5 kHz.
-
Maximum total counting frequency; 20 kHz (A/B phase counter count twice).
Inputs X0 and X1 are equipped with special hardware that allows very high speed 
counting as follows:
-
Single phase or bi-directional counting with C235, C236 or C246; up to 60 kHz.
-
Two phase counting with C251; up to 30 kHz.
If any high speed comparison instructions (FNC’s 53, 54, 55) are used, X0 and X1 must resort
to software counting. In this case, please see the table below: 
I
N
P
U
T
1 Phase counter
user start/reset
1 Phase counter
assigned
start/reset
2 Phase counter
bi-directional
A/B Phase counter
C23
5
C23
6
C23
7
C23
8
C23
9
C24
0
C24
1
C24
2
C24
3
C24
4
C24
5
C24
6
C24
7
C24
8
C24
9
C25
0
C25
1
C25
2
C25
3
C25
4
C25
5
X0 U/D
U/D
U/D
U
U
U
A
A
A
X1
U/D
R
R
D
D
D
B
B
B
X2
U/D
U/D
U/D
R
R
R
R
X3
U/D
R
S
R
U
U
A
A
X4
U/D
U/D
D
D
B
B
X5
U/D
R
R
R
R
R
X6
S
S
S
X7
S
S
S
Function
Number
Max. Combined 
Signal Frequency
53 or 54
11 kHz
55
5.5 kHz
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)
C235