FX Series Programmable Controllers
Basic Program Instructions 2
2-10
2.10
Or Pulse, Or Trailing Pulse
Program example:
Basic points to remember:
-
Use the ORP and ORF instructions for the parallel connection of pulse contacts.
-
Usage is the same as for OR and ORI; see earlier.
-
ORP is active for one program scan after the associated device switches from OFF to
ON.
-
ORF is active for one program scan after the associated device switches from ON to
OFF.
Mnemonic
Function
Format
Devices
Program steps
ORP
(OR Pulse)
Parallel 
connection of 
Rising edge 
pulse
X, Y, M, S, T, C
2
ORF
(OR Falling 
pulse)
Parallel 
connection of 
Falling / trailing 
edge pulse
X, Y, M, S, T, C
2
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)
ORP
Y4
X1
X0
0
LD
M
40
1
ORP
X
1
3
SET
M
50
4
LD
X
0
5
AND
M
24
6
LD
Y
7
7
ORF
X
1
9
ORB
10 OUT
Y
4
M40
ORF
M24
SET M50
X1
Y7
Single operation flags M2800 to M3071:
When used with flags M2800 to M3071 only the first instruction will activate. For 
details see page 2-8