FX Series Programmable Controllers
Basic Program Instructions 2
2-13
2.13
MPS, MRD and MPP
Basic points to remember:
-
Use these instructions to connect output coils to the left hand side of a contact.
Without these instructions connections can only be made to the right hand side of the
last contact.
-
MPS stores the connection point of the ladder circuit so that further coil branches can
recall the value later.
-
MRD recalls or reads the previously stored connection point data and forces the next
contact to connect to it.
-
MPP pops (recalls and removes) the stored connection point. First, it connects the next
contact, then it removes the point from the temporary storage area.
-
For every MPS instruction there MUST be a corresponding MPP instruction.
-
The last contact or coil circuit must connect to an MPP instruction.
-
At  any programming step, the number of active MPS-MPP pairs must be no greater than
11.
Mnemonic
Function
Format
Devices
Program steps
MPS
(Point Store)
Stores the current 
result of the 
internal PLC 
operations
N/A
1
MRD
(Read)
Reads the current 
result of the 
internal PLC 
operations
N/A
1
MPP
(PoP)
Pops (recalls and 
removes) the 
currently stored 
result
N/A
1
FX
0(S)
FX
0N
FX FX
(2C)
FX
2N(C)
MPS
MRD
MPP
MPS, MRD and MPP usage:
When writing a program in ladder format, programming tools automatically add all 
MPS, MRD and MPP instructions at the program conversion stage. If the generated 
instruction program is viewed, the MPS, MRD and MPP instructions are present.
When writing a program in instruction format, it is entirely down to the user to enter all 
relevant MPS, MRD and MPP instructions as required.