8 Preparation for Wiring and Power Supply Wiring Procedures
8.2 Cable Connecting Procedures
8.2.2
Terminal block (for European) [expansion board and special adapters]
The expansion boards and special adapters of a terminal block type have terminal blocks for European.
1. Applicable products
2. Compliant electric wires and tightening torque
*1.
Old model name: CRIMPFOX ZA 3
*2.
Old model name: CRIMPFOX UD 6
3. Treatment of electric wire ends
Treat the ends of stranded wires and solid wires without coating or using bar terminals with insulating sleeve.
Tighten the terminals to a torque of 0.22 to 0.25 N•m.
Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do so may cause
equipment failures or malfunctions.
• Treatment of stranded wires and solid wires without coating
- Twist the ends of stranded wires tightly so that loose wires will not stick 
out.
- Do not solder-plate the electric wire ends.
• Treatment using bar terminal with insulating sleeve
It may be difficult to insert the electric wire into the insulating sleeve 
depending on the thickness of the electric wire sheath. Select the electric 
wire referring to the outline drawing.
<Reference>
*3.
Old model name : CRIMPFOX ZA 3
*4.
Old model name : CRIMPFOX UD 6
4. Tool
For tightening the terminal, use a commercially available small screwdriver
having a straight form that is not widened toward the end as shown right.
Note
If the diameter of screwdriver grip is too small, tightening torque will not be 
able to be achieved. To achieve the appropriate tightening torque shown in 
the table above, use the following screwdriver or appropriate replacement 
(grip diameter: approximately 25 mm (0.98")).
<Reference>
Classification
Model name
Expansion board
FX
3G
-4EX-BD, FX
3G
-2EYT-BD, FX
3G
-485-BD, FX
3G
-2AD-BD, FX
3G
-1DA-BD
Special adapters
FX
3U
-485ADP(-MB), FX
3U
-4AD-ADP, FX
3U
-4DA-ADP, FX
3U
-3A-ADP, FX
3U
-4AD-PT-ADP, FX
3U
-4AD-PTW-ADP,
FX
3U
-4AD-PNK-ADP, FX
3U
-4AD-TC-ADP
Electric wire size 
(stranded wire/solid wire)
Tightening 
torque
End treatment
One electric wire
0.3 to 0.5 mm
2
(AWG 22 to 20)
0.22 to 0.25 N•m
Remove the coating of the stranded wire, twist the core
wires, and connect the wires directly.
Remove the coating from the solid wire, and connect the wire
directly.
Two electric wires 0.3 mm
2
 (AWG 22)
2
Bar terminal with
insulating sleeve
0.3 to 0.5 mm
2
(AWG 22 to 20)
(Refer to the following outline
drawing of bar terminal.)
Bar terminal with insulating sleeve (recommended product)
AI 0.5-8WH: Phoenix Contact
Caulking tool
CRIMPFOX 6
*1
: Phoenix Contact 
(CRIMPFOX 6T-F
*2
: Phoenix Contact)
Manufacturer
Model name
Caulking tool
Phoenix Contact Co., Ltd
AI 0.5-8WH
CRIMPFOX 6
*3
( or CRIMPFOX 6T-F
*4
)
Manufacturer
Model name
Phoenix Contact Co., Ltd
SZS 0.4
2.5
9 mm
(0.36˝)
• Stranded wire/solid wire
• Bar terminal with insulating sleeve
8 mm
(0.32˝)
Contact area
(Crimp area)
14 mm (0.56˝)
2.6 mm
(0.11˝)
Insulating sleeve
0.4 mm
(0.02˝)
2.5 mm
(0.1˝)
With
straight tip