4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.2 Power Supply Specifications
4.1.1
Dielectric withstand voltage test and insulation resistance test
Perform dielectric withstand voltage test and insulation resistance test at the following voltage between each
terminals and the main unit ground terminal.
4.2
Power Supply Specifications
The power supply specifications for the main unit are explained below.
4.2.1
AC power type
*1.
This item shows values when all 24 V DC service power supplies are used in the maximum
configuration connectable to the main unit, and includes the input current (5 or 7 mA per point).
4.2.2
DC power type
*2.
There power consumption values are maximum values which include consumption of all expansion
equipment and input current (5 or 7 mA per point).
Terminal
Dielectric strength
Insulation
resistance
Remark
Terminals of main unit
Between power supply terminal (AC power) and
ground terminal
1.5 kV AC for  1 min
5 M
 or more by 
500 V DC megger
-
Between power supply terminal (DC power) and
ground terminal
500 V AC for 1 min
-
Between input terminal (24 V DC) and ground
terminal
-
Between output terminal (relay) and ground
terminal
1.5 kV AC for  1 min
-
Between output terminal (transistor) and ground
terminal
500 V AC for 1 min
-
Main unit analog input terminal and ground 
terminal
Not allowed
Not allowed
-
Terminals of expansion boards, special adapters
Between terminal of expansion board (except
FX
3G
-4EX-BD and FX
3G
-2EYT-BD) and ground
terminal
Not allowed
Not allowed
Since the expansion board and the main
unit CPU are not insulated, it is not
allowed to perform the dielectric withstand
voltage test and insulation resistance test
between them.
Between FX
3G
-4EX-BD input terminal (24 V DC)
and ground terminal
500 V AC for 1 min
5 M
 or more by 
500 V DC megger
-
Between FX
3G
-2EYT-BD output terminal
 (transistor) and ground terminal
-
Between terminal of special adapter and ground
terminal
-
Item
Specification
FX
3S
-10M/E
FX
3S
-14M/E
FX
3S
-20M/E
FX
3S
-30M/E
Supply voltage
100 to 240 V AC
Allowable supply voltage range 85 to 264 V AC
Rated frequency
50/60 Hz
Allowable instantaneous power
failure time
Operation can be continued upon occurrence of instantaneous power failure for 10 ms or less.
Power fuse
250 V 1 A
Rush current
15 A max.  5 ms or less/100 V AC, 28 A max.  5 ms or less/200 V AC
Power consumption
*1
19 W
19 W
20 W
21 W
24 V DC service power supply
400 mA
Item
Specification
FX
3S
-10M/D
FX
3S
-14M/D
FX
3S
-20M/D
FX
3S
-30M/D
Supply voltage
24 V DC
Allowable supply voltage range 20.4 to 26.4 V DC
Allowable instantaneous power
failure time
Operation can be continued upon occurrence of instantaneous power failure for 5 ms or less.
Power fuse
250 V 1.6 A
Rush current
20 A max.  1 ms or less/24 V DC
Power consumption
*2
6 W
6.5 W
7 W
8.5 W
24 V DC service power supply
-