Partial Shutdown Function with Extension Module 
This function allows to shut off only the outputs of extension module by using safety inputs 
of extension module.
By shutting off only the necessary parts, operating rate of equipment and production line 
can be raised.
Figure 4.5 Partial shutdown with extension module 
The following shows an operation example when the safety relay module system in Figure 
4.5 i
s configured.
 • If SW0, safety input switch of the main module, is pressed, the whole outputs 
(M0, M1, M2, M3) are shut off. 
 • If SW1, safety input switch of the extension module on station number 1, is 
pressed, only output of the extension module (M1) is shut off. 
 • By shorting the safety input of the extension module on station number 3, the 
safety input is synchronized with the safety output of the main module and is 
driven/shut off.
POINT
The safety output of the extension module can be synchronized only with main 
module: therefore; it cannot be synchronized with another extension module.
SW0
SW0
SW1
SW1
SW2
SW2
M3
M2
M2
M1
M3
M0
M1
M0
Safety 
input
Main
module
Extension
module 
Station 
number 1
Extension
module 
Station 
number 2
Extension
module 
Station 
number 3
Short circuit between 
COM and input
Operation diagram
Safety 
input
Safety 
input
Safety 
input
Safety 
input
Safety 
input
Safety 
input