Справочник Пользователя для Mitsubishi Electronics -QS90SR2SN-Q

Скачать
Страница из 96
5
SETTINGS AND PROCEDURES BEFORE 
OPERATION
5.2 CC-Link Safety Relay Module
5.2.3 Part names and settings
5
 - 12
1
O
V
ER
VI
E
W
2
S
YST
EM
 
CONF
IGURA
T
ION
3
S
P
E
C
IF
ICA
T
IONS
4
F
UNCT
IO
NS
5
S
E
T
T
INGS
 A
ND 
PR
O
C
E
DURES
 BEF
ORE 
OP
E
R
A
T
ION
6
T
R
O
U
BL
ESH
O
O
T
ING
AP
PENDI
X
5.2.3
Part names and settings
This section explains each part name of the CC-Link safety relay module.
Figure 5.8 CC-Link safety relay module
Table 5.2  Part names (1/2)
Number
Name
Description
1)
Indicator LED
PW
Indicates status of the module power supply.
ON:
Module power supply is supplied.
OFF:  Module power supply is cut off or powered OFF with electric fuse.
ERR.
Indicates an error of the station.
Flash: A self-diagnostics error has occurred or safety power supply is cut 
off.
OFF: Normal
L RUN
Indicates communication status of the CC-Link system.
ON:
Normal communication
OFF:  Communication is cut off (time over error).
SD
ON:
During data transmission
RD
ON:
During data reception
L ERR.
Indicates a communication error in the CC-Link system.
ON:
A value set with station number setting switch or 
transmission speed setting switch is out of range.
Flashing regularly:
The station number setting switch or transmission 
speed setting switch is changed during operation.
Flashing irregularly: A terminating resistor is not attached, is attached 
wrongly or is influenced by noise.
OFF:
Normal communication
S PW
Indicates the status of the safety power supply.
ON:
Safety power supply is supplied.
OFF:  Safety power supply is cut off or powered off with an electric fuse.
1)
7)
11)
3)
6)
8)
2)
5)
1)
9)
10)
4)
6)