4.2 Start-up/off Check Function
 
4
FUNCTIONS
4.2
Start-up/off Check Function
This function is to start the system after making sure that status of the safety relay module 
and external device are normal.
When the safety relay and electromagnetic switch are connected, connecting the normally 
closed contacts to the start-up/off check terminal of the safety relay module inhibiting the 
start-up at a failure such as contact welding.
Figure 4.2 Off check function
Figure 4.3 Timing chart
POINT
 • Connect normally closed contact of forcibly guided type electromagnetic 
switch to off check.
 • If connecting normally closed contact of electromagnetic switch other 
than forcibly guided type, contact separation of the electromagnetic 
switch cannot be detected.
 •  Wire the start-up/off check input so that the external wiring length can be 
50m (164.04 feet) or less.
 • The timing of safety input and start-up/off check are inconstant. 
Therefore, control using this timing cannot be made.
Safety relay 
module
Off check
Start-up 
command
Safety status
Safety 
output
Power, etc.
Electromagnetic 
switch 
Non-safety part
Start-up switch
Emergency stop 
switch
Light curtain,
etc.
The start-up switch turns on.
(Manual mode)
Short circuit
Open
Open
Short circuit
OFF
OFF
ON
ON
OFF
Short circuit
Open
Open
Short circuit
Activation state
Activation state
Safety output
Start-up input
(XS0-XS1)
Off check input
Safety input
(X0-COM), (X1-COM)