5.1 Q Series Safety Relay Module
5.1.2 Handling precautions
5
SETTINGS AND PROCEDURES BEFORE 
OPERATION
5.1.2
Handling precautions
This section explains handling precautions for the Q series safety relay module.
(1) Module fixing screw
Tighten the module fixing screws and terminal block mounting screws within the 
following torque range.
WARNING
● Do not touch the terminals while power is on.
Doing so could result in electric shock.
● Turn off all phases of the external supply power used in the 
system when cleaning the module or retightening the 
terminal block mounting screws or module mounting screws.
Not doing so could result in electric shock.
Tighten a terminal block mounting screw and module 
mounting screw within the specified torque range.
If the terminal block mounting screw is too loose, it may 
cause a short-circuit, fire or malfunctions.
If too tight, it may damage the screw and/or the module, 
resulting in a drop of the screw or module, a short circuit, or 
malfunctions.
If the module mounting screw is too loose, it may cause a 
drop of the screw or module.
Over tightening the screw may cause a drop due to the 
damage of the screw or module.
CAUTION
● Be sure there are no foreign substances such as sawdust or 
wiring debris inside the module.
Such debris could cause a fire, failure, or malfunctions.
● Do not disassemble or remodel the module.
Doing so could cause a failure, malfunctions, injury, or fire.
If the product is repaired or remodeled by other than the 
specified FA centers or us, the warranty is not covered.
● Do not directly touch the module's conductive parts or 
electronic components.   
Doing so may cause malfunctions or a failure.
● When disposing of this product, treat it as industrial waste.
Screw
Specified torque range
Module fixing screw (M3)
0.36 to 0.48N m
Terminal block mounting screw (M2.6)
0.20 to 0.30N m