Справочник Пользователя для Mitsubishi Electronics #NAME?

Скачать
Страница из 96
5
 - 19
5.3 Extension Safety Relay Module
5.3.3 Part names and settings
5
SETTINGS AND PROCEDURES BEFORE 
OPERATION
Table 5.3 Part names (2/2)
Number
Name
Description
4)
Start-up part terminal block
XS
XS0, XS1: Start-up/off, check terminal
5)
Safety output part terminal block
Z00, Z01: Safety relay output terminal
Z10, Z11: Safety relay output terminal
Z20, Z21: Safety relay output terminal
6)
Extension communication 
station number setting switch
LOCAL ST No.
A switch for setting the station number of extension communication
Set a station number within the range from 1 to 3.
Setting 0 causes an error.
7)
Extension communication 
terminating resistor setting 
switch
LT
Switch 1: Reserved
Switch 2
ON: Terminating resistor is attached.
OFF: Terminating resistor is not attached.
8)
Start-up mode setting switch
A switch for setting start-up input mode
"A" side: Auto mode
"M" side: Manual mode
9)
Safety part extension connector IN, OUT
A connector for connecting an extension module
IN: A connector for connecting a module to the previous module with a safety 
circuit part extension cable at extension
OUT: A connector for connecting a module to the next module with a safety 
circuit part extension cable at extension
10)
Serial number display
A serial number same as the one shown on the rating plate
Setting
Setting switch status (LOCAL ST No.)
8
4
2
1
1
Disabled
Disabled
OFF
ON
2
Disabled
Disabled
ON
OFF
3
Disabled
Disabled
ON
ON