6.3 Extension Safety Relay Module
6.3.1 Error check method with LED
6
TROUBLESHOOTING
6.3
Extension Safety Relay Module
6.3.1
Error check method with LED
Table 6.5 shows description, cause investigation, and corrective action of errors 
depending on LED display on the module.
: ON,  : Flash,  : OFF, *: ON or OFF
 * 1: The status that start-up processing has been performed to the module
Table 6.5 Error handling of safety part with LED
LED signal 
Cause
Corrective action
PW
ERR.
Z
K1
K0
X1
X0
Normal (before start-up)
-
Normal (started up)
-
*
*
The module power supply is not normally 
supplied.
•Check if the power supply is normally 
supplied.
•Check between the power supplies for 
short.
•In case of input N type, check between 
the dual inputs for short.
*
*
Contact welding of K0 and K1 relays
•Replace the module.
K0 and K1 relays do not turn ON.
*1
Safety system 1 does not turn ON.
*1
Safety system 2 does not turn ON.
*1
Safety system 1 does not turn OFF.
*1
Safety system 2 does not turn OFF.
*1
*
*
*
*
*
*
•System error occurred.
•The safety power supply is not normally 
supplied.
•Check if the power supply is normally 
supplied.
•Check between the power supplies for 
short.