7000 Bus Converter User Manual (version 1.2,Feb/2003, 7PH-006-10)  --------------- 73 
6.   7000 RS-485 Networking 
6.1  Standard/Isolation Configuration 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The Host PC/PLC will send out a command string from its RS-232 
port. The 
7520 will convert these RS-232 signals into a RS-485 signal 
and isolate the host from 
RS-485 network. 
The 7000 series modules, including D/I, D/O, A/D, D/A, 
Timer/Counter and MMI modules, will be directly connected to 
RS-485. 
These 7000 series modules can connect a max. Of 256 modules to the 
RS-485 network without a repeater, the 7510. That it to say, there can 
be 256 modules from 
7xxx to 7xxx. If there are over 256 modules, the 
repeater 7510 must be added to extend the 
RS-485 to RS-485. Then 
there can be another 256 modules connected to the 
RS-485 network. 
This is the first function of the 7510. 
 
The module address can be changed from 00 to FF a total of 256 
max. Therefore there are maxes. Of 256 modules in one RS-485 network 
if all the modules communicate with the same speed.  
(1) 
Because the 7000 can communicate with different baud rates in the 
same RS-485 network, the 
7xxx,  7xxx and 7xxx can be 
communicated to HOST PC/PLC with a different baud rate. 
(2) 
The 7000 series can be programmed to 1200, 2400, 4800, 9600, 
19200, 38400, 57600, 115200,a total of 8 different speed. 
(3) 
The 7000 modules can share the same module address if their baud 
 
 
 
7520, isolated 232/485 converter 
RS485 
 
  
RS485
Standard Configuration.
 
 
 7xxx 
7xxx 
~<=256
 7xxx 
~<=2048
 
 
Host 
PC 
PLC 
RS232 
 
   
RS485 
Max 2048 7xxx 
modules in one 
RS-485 network 
RS-485
 
RS-485
 
7510, isolated 485/485 repeater
D+
D-
 
D+
D-
 
Is terminator 
Gnd