3 - 8
MELSEC-A
3   SPECIFICATION
3.4 Function List
The AJ65SBT-64AD function list is shown in table 3.3.
Table 3.3 AJ65SBT-64AD function list
Item
Description
Refer to
Sampling processing
Perform A/D conversion of an analog input value one by one and store the result into
the remote register each time.
Section 3.4.1
Section 3.5.2
Moving average
processing
Average the digital output values of the specified count measured per sampling time.
Section 3.4.2
Section 3.5.2
Section 3.6.4
A/D conversion
enable/prohibit
specification
Specify whether A/D conversion is enabled or disabled per channel.
By prohibiting the conversion for the channels which are not used, the sampling time
can be shortened.
Section 3.6.2
Can set the analog input range per channel to change the I/O conversion
characteristics.
Select the input range setting from among the following 8 types.
Input Range
Set Value
-10 to +10V
0H
0 to 5V
1H
1 to 5V
2H
0 to 20mA
3H
4 to 20mA
4H
User range setting 1 (-10 to +10V)
5H
User range setting 2 (0 to 5V)
6H
User range setting 3 (0 to 20mA)
7H
Input range changing
function
Section 3.6.3
Offset/gain setting
The offset/gain setting can be performed volumeless for each channel, and the I/O
conversion characteristics can be changed.
Section 4.4