3   SPECIFICATION
3.6.3 Input range setting (Address RWwm+1)
(1)   Set the analog input range per channel.
(2)   Operation is performed according to the setting made for the leading edges of the
initial data setting request flag (RY(n+1)9).
(3)   The default setting is -10 to +10V for all channels.
b15
b12
b11
b8
b7
b4
b3
b0
to
CH.4
to
CH.3
to
CH.2
to
CH.1
Input Range
Set Value
-10 to +10V
0H
0 to 5V
1H
1 to 5V
2H
0 to 20mA
3H
4 to 20mA
4H
User range setting 1 (-10 to +10V)
5H
User range setting 2 (0 to 5V)
6H
User range setting 3 (0 to 20mA)
7H
(4)   When making offset/gain setting, set all channels to any of "user range settings 1
to 3".
Setting any other range will result in an error and flicker the "RUN" LED at 0.1s
intervals.