TIC-LF654L 
 
 Model LF620 and LF622 converters 
Input signals 
Analog signal  the voltage signal from detector, 
proportional to process flow rate (for LF622 
separate type converter). 
Digital input DI  
Signal type:  20 to 30Vdc voltage signal 
Input resistance: 2.7k
 
Number of inputs: one point 
Note: DI cannot be used with the Modbus communication. 
DI function — One of the following functions can 
be assigned to the DI signal. 
Range switching — Selects either the higher or 
lower range in the unidirectional or bidirectional 
2-range setting. 
Totalizer control — ‘Starts and stops’ or ‘Rest and 
start’ the built-in totalizer. 
Fixed-value outputs —Outputs fixed-values for 
current and pulse outputs for loop check. 
Zero adjustment — Executes zero adjustment 
(on-stream at zero flow rate). 
Output signals 
Current output: 
4–20mAdc (load resistance 0 to 750
) 
Note: The current output cannot be used with the 
PROFIBUS-PA communication.                                  
(Refer table 6 for details) 
Digital outputs — Two points are available as 
follows. 
Digital output DO1: 
Output type: Transistor open collector 
Number of outputs: One point 
Output capacity: 30Vdc, 200mA maximum  
Note: DO1 cannot be used if Modbus 
communication connection is 3 lines.       
(Refer table 6 for details) 
Digital output DO2 : 
Output type:  
Solid-state relay output (non polarity) 
Number of outputs: One point 
Output capacity: 150Vdc, 150mA maximum or 
150Vac (peak to peak), 100mA maximum  
Note: DO2 cannot be used with the Modbus 
communication. (Refer table 6 for details) 
DO1 and DO2 functions — One of the following 
functions can be assigned to DO1 and/or DO2 . 
• Pulse output (available only for DO1, DO2) 
Pulse rate: MAX 10kHz (10000pps)(DO1) 
MAX 100Hz (100pps)(DO2) 
(Over 1kpps, auto-setting) 
Pulse width: 0.5 to 500ms (but less than half of 
the period for 100% flow rate) 
Note: The same and simultaneous pulse is not available 
between DO1 and DO2.) 
• Multi-range selection outputs (Note 1) 
• High, High high, Low, and/or Low low alarm 
outputs (Note 2) 
• Empty pipe alarm output (Note 2) 
• Preset count output 
• Converter failure alarm output 
Note 1:  Two outputs (DO1 and DO2) are needed for 4-range 
switching and forward/reverse 2-range switching. 
Note 2: Normal Open (default set) or Normal Close is selected 
for alarm outputs when programming. 
When power failure occurs, unit will be fault to Normal 
Open. 
Communications output: 
• HART (std.) — Digital signal is superimposed on 
4–20mAdc current signal as follows: 
Conforms to HART protocol 
Load resistance: 240 to 750
 
Load capacitance: 0.25µF maximum 
Load inductance: 4mH maximum 
• PROFIBUS (opt.) 
Protocol: PROFIBUS-PA 
Baud rate: 31.25kbps 
Bus voltage: 9-30VDC 
Consumption electric current of bus: less than 16mA 
Manufacture Ident-No.: 093B
HEX 
Standard Ident-No.: 9740
HEX
 
Slave address: 0-126 (Default address is 126) 
Profile: Profile Ver.3.01 for Process Control 
Devices 
Function blocks: AI(Flow)×1 , Totalizer×1 
• MODBUS (opt.) 
Physical layer : RS485 
Protocol : Modbus 
Mode : RTU 
Baudrate : 4800, 9600, 19200bps 
Data length : 8bit 
Parity bit : None, Odd, Even 
Stop bit : 1bit, 2bit 
Error check : CRC-16 
Max. station number : 32(with Master device) 
Max. cable length : 1.2km (Note) 
Note: This length is specification of 3 line 
connection.