GE GFK-0804B 用户手册

下载
页码 160
2
2-4
Micro PLC Programmer’s Guide – April 1994
GFK-0804B
Creating a Program Rung
Select Rung Create (F1) to create a new program rung. If there are already rungs in the
program, the new rung will appear at the top of the page.
You can now enter a program element in the highlighted location. Use the ESC key if
you want to return to a previous menu.
In the Edit window, use the function keys to select a program element.
–| |–  (F1)
Normally-open contact. See page 4-4.
–| |–   (Shift, F1)
Positive transition contact. See page 4-4.
–| / |–    (F2)
Normally-closed contact. See page 4-4.
–| #|–   (Shift, F2)
Negative transition contact. See page 4-4.
–(
)–   (F3)
Output. See page 4-11.
Timer/Counter (F4)
Timer or Counter. See pages 4-16 and 4-19.
Math/Move (F5)
Math or Move function. See pages 4-22 and 4-30.
Comp (F6)
Compare function. See page 4-36.
E. Lbl (Shift, F6)
Element label. See page 2-8.
Logic (F7)
Logic function. See page 4-38.
R. Lbl (Shift, F7)
Rung label. See page 2-8.
________  (F8)
Draw horizontal (serial) line. See page 2-7.
 
(F9)
Draw or erase vertical (parallel) line. See page 2-7.
Accept (F10)
Exit editing a rung. See page 2-6.
Clear  (Shift, F10)
Delete (clear) the rung being edited.  Be careful. 
Note
: the Delete key on your keyboard will remove the
element at the current position in either Rung Edit or
Rung Create mode.