PAGE 16                                                         06 Apr 2000                                                 CH. 2:  TIU050
GFK-1819
2.4 TIU050 
Ports
2.4.1 
TIU050 Configuration of the RS-485 Port
The configuration bank (shown in Figure 2.5) sets the parameters of the RS-485 port as described in
Table 2.1.
Table 2.1 – Configuration Bank
Switch 1
ON: Pull-up (must be used together with switch 3)
OFF: no Pull-up
Switch 2
ON: 120
Ω
 termination
OFF: no termination
Switch 3
ON: Pull-down (must be used together with switch 1)
OFF: no Pull-down
Switch 4
Reserved for future use
NOTE: Switch 1 and 3 must be used together.  Either both pull-up and pull-down are
used or neither is used.
Figure 2.3 – Power Connector
Powered by +24VDC and Ground.
Figure 2.4 – Configuration Bank
O F F
O N
S W 1
Figure 2.2 – Automation Equipment Serial Port
Pin 1
Pin 8
TIU050 8-pin Terminal Block