Delta DT3 用户手册

下载
页码 21
 
 
1
 
DT3 Series Temperature Controller Instruction Sheet
 
 Precaution 
  DANGER! Caution! Electric Shock! 
 
1. 
Do not touch the AC terminals while the power is supplied to the controller to prevent an electric shock. 
2. 
Make sure power is disconnected while checking the unit inside. 
 
WARNING!
 
 
This controller is an open-type temperature controller. Make sure to evaluate any dangerous application in which a 
serious human injury or serious property damage may occur. 
1. 
Always use recommended solder-less terminals: Fork terminal with isolation. (M3 screw, width is 6.0mm)   
2. 
Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning. 
3. 
Never modify or disassemble the controller. 
4. 
Do not connect anything to the “No used” terminals. 
5. 
Make sure all wires are connected to the correct polarity of terminals. 
6. 
Do not install and/or use the controller in places subject to: 
y
 Dust or corrosive gases and liquid    y High humidity and high radiation   
y
 Vibration and shock              
   
 
y
 High voltage and high frequency 
7. 
Must turn power off when wiring and changing a temperature sensor. 
8. 
Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires.
9. 
Please use wires with resistance when extending or connecting a platinum resistance thermometer (RTD). 
10.  Please keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller and please 
route power wires as far as possible from load wires to prevent interference and induced noise. 
11.  This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping water, 
corrosive materials, airborne dust and electric shock or vibration. 
12.  Please make sure power cables and signals from instruments are all installed properly before energizing the controller, 
otherwise serious damage may occur. 
13.  Please do not touch the terminals in the controller or try to repair the controller when power is applied to prevent an electric 
shock. 
14.  Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any internal 
circuit within this period. 
15.  Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.
 
 
 Display, LED & Pushbuttons   
 
 
 
 
Odering Information 
 
 
DT3 Series 
DT3: Delta 3 Series Temperature Controller 
 
Panel Size (W×H) 
20: 4848 1/16 DIN W48 × H48mm 
30: 7272 W72 × H72mm 
40: 4896 1/8 DIN W48 × H96mm 
60: 9696 1/4 DIN W96 × H96mm 
  1st output group selection 
R: Relay Output, 250 VAC, 5A 
V: Voltage Pulse Output, 12V ±10% 
C: DC Current Output, 4 ~ 20 mA   
L: Linear Voltage Ouptut 0 ~ 10 VDC 
  Power supply  
A: AC 80 ~ 260 V   
D: DC 24 VDC 
  2nd output group selection 
0: None 
R: Relay Outupt,250 VAC, 5A