Honeywell MRP-2001E 用户手册

下载
页码 136
Input-to-Output Circuit Mapping and Cross-Zone Operation
Circuit Mapping and Cross-Zoning
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
105
A.1.2  Mapping Input Zones to Release Circuits for Cross Zone
           Activation
Using the OUTPUT CIRCUITS menus, this fire panel will allow you to assign a release circuit type 
of operation to any two of the four output circuits.  Up to two releasing circuits (or hazards), called 
RELEASE 1 and RELEASE 2, may be created.  Input zones may be assigned in various ways to 
activate either one or both of the release circuits.  The fire panel treats RELEASE 1 and RELEASE 
2 functions independently from each other, although they may share input circuits for activation.
Cross-zoning is set up in the CROSS INPUT ZONES menus, where you can create up to three 
groups of input zones for each release circuit.  When cross zone groups have been set up, the 
OUTPUT CIRCUIT MAP  associated with the input zones will automatically show YES for release 
output circuits.  This extremely flexible cross-zone with grouping capability is used in the 
following examples.
Example 3: A single hazard, cross-zoned application using two smoke detector input zones and 
one releasing output circuit.  Input Zones 1 and 2 are cross-zoned to activate output circuit 2, which 
is programmed as a RELEASE 1.   
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
Output Circuit 3 is programmed as alarm NAC using the OUTPUT CIRCUITS menus
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
Either of smoke detector Input Zones 1 or 2 will directly activate Output Circuit 1 (Alarm 
NAC).  
Smoke detector Input Zone 2 will also directly activate Output Circuit 3 (Alarm NAC) but 
not Output Circuits 2 or 4.
Smoke detector Input Zones 1 and 2 are cross-zoned (both must be in alarm) to activate 
Output Circuit 2 (Release 1) but not Output Circuit 4.
                ZONE 1 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
               OUTPUT MAP ZONE 1
1=ALARM NAC                         YES
2=RELEASE 1                          YES
3=ALARM NAC                          NO
               OUTPUT MAP ZONE 1
1=SUPV BELL NAC                 N/A
           REL 1 CROSS GROUP 1
1=ZONE 1                                  YES
2=ZONE 2                                  YES
3=ZONE 3                                  NO
               OUTPUT MAP ZONE 2
1=SUPV BELL NAC                 N/A
                ZONE 2 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
               OUTPUT MAP ZONE 2
1=ALARM NAC                         YES
2=RELEASE 1                          YES
3=ALARM NAC                          YES