Honeywell MRP-2001E 用户手册

下载
页码 136
Installation
ANN-BUS Devices
34
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
2.7.3 ANN-80 Remote LCD Annunciator
The ANN-80 LCD Annunciator is a compact, 80 character, backlit LCD remote fire annunciator 
which mimics the FACP display.  It also provides system status indicators for AC Power, Alarm, 
Trouble, Supervisory and Alarm Silenced conditions.  Communication between the ANN-80 and 
FACP is accomplished over a two wire serial interface employing the ANN-BUS communication 
format.  The devices are powered, via two additional wires, from either the host FACP or remote 
UL-listed, filtered, power supply.
2.7.4 Specifications
Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
 Normal/Standby (no activity): 37.0 mA
 Trouble: 39.0 mA
 Alarm: 40.0 mA
 AC Fail (not backlit): 15.0 mA
For use indoors in a dry location
2.7.5 Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the 
annunciator.
2.7.5.1 Mounting
The ANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical 
box.  Select and remove the appropriate knockout(s), pull the necessary wires through the 
knockouts and mount the annunciator in or on the wall depending on the type of installation 
desired.
The ANN-80 cover must be attached to the annunciator backplate before mounting the 
annunciator to the electrical box/wall.  The cover cannot be reattached or removed after the 
annunciator has been mounted. 
2.7.5.2 Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the 
terminal block and DIP switches (refer to figure below):
1. Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise
2. Push in the snap latch located on the right side of the unit while pulling the cover open
3. To close the cover, make certain the key switch is in the ON (Unlocked) position.  Swing the 
cover closed, snapping it shut
4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key
Key switch shown in ON position
Press in latch and pull 
annunciator cover open
Annunciator cover with LCD display
Annunciator backplate