Testing & Maintenance
Testing
124
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
APPENDIX E 
 
Testing & Maintenance
E.1  Testing
E.1.1  Inspection
Once installation has been completed, a careful visual inspection should be made before applying 
power to the system.  Check the actual wiring hookup with the wiring diagrams.  Insure that no 
pieces of wire have fallen into the circuitry.  Check for missing or damaged parts.
E.1.2  Alarm Test
An initial alarm test should be conducted following installation to determine that all parts of the 
system are functioning properly.  The panels should remain powered for 24 to 36 hours prior to 
connecting the releasing solenoids.  This precaution will avoid false activation of the suppression 
system in case of faulty or improperly placed detectors.
To perform an alarm test on the control panel, proceed with the following steps:
1. Disconnect AC power and battery power
2. Disconnect the installed solenoid valve circuit leads and connect spare solenoid valves or 
connect an End-of-Line device to serve as a dummy load
3. Reconnect AC and battery power
4. Initiate a first zone alarm condition by introducing smoke into one of the Zone 1 detectors.  
This should cause the first zone alarm condition
 The red Fire Alarm indicator will illuminate
 The LCD display will indicate an alarm condition for zone 1
 The control panel piezo will sound
 The Alarm relay will energize
 The devices connected to the Indicating Circuit(s) programmed to activate on Zone 1 
alarm will turn on
5. Repeat step 4 for each input zone
6. When testing has been completed, remove AC and battery power, reconnect the solenoid 
valve circuits removed in step 2, reconnect AC and battery power and ensure that the control 
panel is in normal standby condition
5.4.3 Detector Testing
Detectors must be tested after installation and following maintenance.
Important:  Before testing, notify the proper authorities that maintenance is being performed and 
the system will be temporarily out of service.  Disable the zone or system undergoing maintenance 
to prevent any unwanted alarms.  Disconnect the installed solenoid valve circuit leads and connect 
spare solenoid valves or connect an End-of-Line device to serve as a dummy load to prevent 
unwanted water release.
Ensure proper wiring and power is applied.  After power-up, allow 80 seconds for the detectors to 
stabilize before testing.  Refer to System Sensor’s i
3
 Installation and Maintenance Instructions 
document I56-1800-00 for device specifications and testing procedures.