XR10 Programming Guide
6.1
SYSTEM OPTIONS
This section allows you to select system wide functions of the XR10 system.
6.2
ALL/PERIMETER
YES configures the panel as a Perimeter (Area 1) and Interior (Area 2) system.
NO configures the panel for Home/Sleep/Away operation. In addition to the Perimeter (Area 1)
and Interior (Area 2) a third area, Bedrooms (Area 3) is created. Zones must be assigned to
Bedrooms for the area to be active.
6.3
CLOSING CODE
When YES is selected, a code number is required for system arming. If NO is selected, a
code number is not required for system arming.
6.4
ENTRY DELAY 1
Enter the Entry Delay time for all Exit type zones programmed to use Entry Delay 1. When an
armed Exit type zone is faulted, the keypad prewarn tone begins sounding and ENTER
CODE: -  
displays on all keypads.
The area must be disarmed before the Entry Delay time expires or an alarm will occur on the
entry zone. All Burglary type zones in all areas are delayed along with the Exit zone during the
Entry Delay. Entry delay times can be from 1 to 250 seconds in one second increments.
Repeat the above for Entry Delay 2 if it is being used.
6.5
EXIT DELAY
Enter the Exit Delay time for all Exit type zones. When the system is armed, this Exit Delay
time starts and all activity on Exit and Burglary zones is ignored until the Exit Delay expires.
This delay countdown is displayed on the keypad for the user.
If an Exit type zone is in a bad condition at the end of the Exit Delay:
the alarm bell sounds for 15 seconds
an Exit Error report is sent to the alarm receiver
the bad Exit type zone is force armed
If any other zone is in a bad condition at the end of the Exit Delay, an alarm on that zone is
indicated. The Exit Delay time can be from 1 to 250 seconds in one second increments.
Enter zero to disable the Exit Delay feature.
6.6
CROSS ZONE TIME
Enter the time allowed between zone faults. When a zone programmed for cross zoning
faults, the panel begins counting down the Cross Zone Time you enter here. If the same zone
or another zone faults within this time, an alarm report is sent to the receiver.
If the Cross Zone Time expires without the second zone fault, only a zone fault report from the
first zone is sent to the receiver. The Cross Zone Time can be from 4 to 250 seconds in one
second increments.
Enter zero to disable the Cross Zone Time feature.
6.7
POWER FAIL DELAY
This option allows you to delay the reporting of an AC power failure. When the AC power is off
for the length of the programmed delay time, an AC power failure report is sent to the
receiver. The delay time can be from 1 to 9 hours. Entering a zero sends the AC power failure
report within 15 seconds.
6.8
RESET SWINGER BYPASS
When YES is selected, a swinger bypassed zone is reset if it remains in a normal condition for
one hour after being bypassed. A report of the automatic reset is sent to the receiver if Bypass
Reports has been selected as YES. See section 5.5.
6 - SYSTEM OPTIONS
ALL/PRM
YES
SYSTEM OPTIONS
ENTRY DLY  1:       30
ENTRY DLY  2:       60
EXIT  DELAY:       45
CLS CODE  NO
PWR FAIL HRS:    1
CRS ZONE TM:        0
RST SBYP           YES