Omron FQM1-MMP21 用户手册

下载
页码 414
148
Pulse Inputs
Section 7-5
7-5
Pulse Inputs
7-5-1
Applicable Models
7-5-2
Outline
The FQM1-MMP21 and FQM1-MMA21 Motion Control Modules can receive
pulse inputs. The following table shows the processes that can be performed
by combining the pulse input function with the high-speed counters to count
pulse signals from a rotary encoder or other device and perform processing
based on the counter PV.
Note
Interrupts cannot be generated for range comparisons. Only bit patterns are
output.
The high-speed counter PV movement during a fixed time interval (equivalent
to the travel distance) and the high-speed counter’s frequency can also be
monitored as required.
7-5-3
Specifications
Model
Functions
FQM1-MMP21
Motion Control Module for Pulse I/O
FQM1-MMA21
Motion Control Module for Analog I/O
Process
Description
Target value comparison 
interrupts
An interrupt task is executed when the high-speed 
counter PV equals a preset target value.
Bit pattern outputs for 
range comparisons
When the high-speed counter PV is within a specified 
range, the user-set bit pattern specified in the compari-
son table is output internally. 
Measurement
modes 1 and 2
Movement in the high-speed counter or input pulse 
counting speed can be displayed while monitoring the 
high-speed counter PV. 
High-speed counter PV 
latch
High-speed counters 1 and 2 each have a latch register. 
Two latch inputs can be used to capture the high-speed 
counter PVs at high speed. 
Item
Specification
Number of counters
2
Pulse input operation mode 
(Set in System Setup.)
Phase differential
Increment/decrement
Pulse + direction
Input pin 
numbers
High-speed 
counter 1
High-speed 
counter 2
24 V: 1 (5)
LD: 3 (5)
24 V: 2 (6)
LD: 4 (6)
Phase A
Increment pulse
Pulse
24 V: 7 (11)
LD: 9 (11)
24 V: 8 (12)
LD: 10 (12)
Phase B
Decrement pulse
Direction pulse
24 V: 13 (17)
LD: 15 (17)
24 V: 14 (18)
LD: 16 (18)
Phase Z
Reset pulse
Reset pulse
Input method
Phase differential 
×1, 
×2, or ×4 (switchable)
Single-phase 
×2
Single-phase + direc-
tion
Set in the System Setup.
(Set input for pulse input counter 1 and counter 2.)
Counting speed (Set separately for each 
port in the System Setup.)
50 kHz (default) or 500 kHz (2 MHz when using phase differential
 ×4)
Counter operation
Linear Counter or Circular Counter (Set in the System Setup.)