Pulse Outputs
Section 7-6
7-6-8
Time Measurement with the Pulse Counter
The one-shot pulse output function can be used to create a high-precision
pulse counter timer.
To measure time with high-precision, start the timer by executing the
STIM(980) instruction with C1 = 000B or 000C and C2 = 0000, and stop the
timer by executing STIM(980) with C1 = 000B or 000C and C2 = 0001.
The timer’s elapsed time is stored in 8-digit hexadecimal in words A621 and
A620 (pulse output 1) or A623 and A622 (pulse output 2). When the timer
starts, the corresponding words are initialized to 0000 0000 hex and the con-
tent is incremented as time passes. The final value is retained when the timer
stops. 
Set the pulse output operation mode to Calculation (time measurement) in
advance in the System Setup, as shown in the following table.
Note
(1) The external pulse output from the port is disabled when this mode is se-
lected. 
(2) A pulse output port that is being used as a pulse counter timer cannot be
used for any other pulse output functions. 
Word
Bits
Function
Contents
A620
00 to 15
Pulse time 
measurement 
1
Lower 
4 digits
Contains the pulse counter’s time mea-
surement in 8-digit hexadecimal.
The content can range from 0000 0000 
to FFFF FFFF hex.
Note These words are refreshed dur-
ing the Motion Control Module’s 
I/O refreshing.
A621
00 to 15
Upper 
4 digits
A622
00 to 15
Pulse time 
measurement 
2
Lower 
4 digits
These words function just like the 
words for pulse time measurement 1, 
described above.
A623
00 to 15
Upper 
4 digits
Tab page
Function
Details
Pulse Output
Pulse output 1 
− Operation mode Calculation (time measurement)
Pulse output 2 
− Operation mode
Counting mode
(Time measurement) 
Timer start condition
Timer stop condition
Timer started by executing
STIM with C2 = 0000.
Timer stopped by executing
STIM with C2 = 0001.
Timer PV in
A620 and A621
or A622 and A623
Elapsed time
PV reset
PV held
Time