Omron FQM1-MMP21 用户手册
235
Connecting the CX-Programmer
Section 8-2
8-2
Connecting the CX-Programmer
8-2-1
System Configuration
Connecting a Personal Computer Running Support Software
Connecting to the Peripheral Port
Connecting to the RS-232C Port
Programming Software
Note
When the CX-Programmer is used with an FQM1, the CX-Programmer ver-
sion must be Version 5.0 or higher and the FQM1 Patch Software must be
installed.
sion must be Version 5.0 or higher and the FQM1 Patch Software must be
installed.
Computer
Windows
OS
Computer connector
D-Sub, 9-pin
D-Sub, 9-pin
D-Sub, 9-pin
D-Sub, 9-pin
D-Sub, 9-pin
Length
0.1 m
2.0 m
6.0 m
2.0 m
6.0 m
Peripheral port
RS-232C
Peripheral port
CS1W-CN118
Cable
CS1W-CN118
(See note 1.)
CS1W-CN226
CS1W-CN626
CS1W-CN626
CM MM
MM
CM
Computer
(RS-232C, 9-pin)
(RS-232C, 9-pin)
Connecting Cables for Peripheral Port
1.
The CS1W-CN118 Cable is used with an RS-232C cable to connect to the peripheral port on the
Coordinator Module as shown below. Peripheral bus communications cannot be used if the CS1W-CN118
Cable is combined with an RS-232C Cable that has a model number ending in -V. In this case, Host Link
(SYSMAC WAY) communications must be used.
Coordinator Module as shown below. Peripheral bus communications cannot be used if the CS1W-CN118
Cable is combined with an RS-232C Cable that has a model number ending in -V. In this case, Host Link
(SYSMAC WAY) communications must be used.
Note
XW2Z-
@@@S-@@
(See note 2.)
RS-232C Cable
2.
Host Link (SYSMAC WAY) communications cannot be used. Use peripheral bus communications.
CM
MM
Note
Computer
(RS-232C, 9-pin)
(RS-232C, 9-pin)
RS-232C Cable
XW2Z-200S-CV or XW2Z-200S-V: 2 m
XW2Z-500S-CV or XW2Z-500S-V: 5 m
XW2Z-500S-CV or XW2Z-500S-V: 5 m
The XW2Z-200S-CV and XW2Z-500S-CV use static-resistant
connectors and can be connected through peripheral bus or Host
Link communications. The XW2Z-200S-V and XW2Z-500S-V,
however, can only be connected through Host Link, not through
peripheral bus.
connectors and can be connected through peripheral bus or Host
Link communications. The XW2Z-200S-V and XW2Z-500S-V,
however, can only be connected through Host Link, not through
peripheral bus.
RS-232C port
OS
Name
Microsoft Windows
CX-Programmer Version 5.0 or higher only
(See note.)
(See note.)
CD-ROM